Partial blockages in water pipe networks may contribute to large energy dissipation throughout the system and reduce the service effectiveness for the customers. In this paper, a recently developed stochastic model using transient head measurements for detecting partial blockages in water pipelines is tested with two experimental case studies. The model is a stochastic Successive Linear Estimator (SLE, Yeh et al. 1996) previously used in groundwater hydrology for detecting the heterogeneity pattern of the subsurface. The model provides statistically the best unbiased estimate of diameter distribution due to partial blockages and quantifies the uncertainty associated with these estimates. Tests were carried out at the Water Engineering Laboratory of the University of Perugia (WEL) on two high density polyethylene pipe systems. In the experiments the partial blockages were simulated by placing a smaller diameter pipe of two different lengths between the main pipe. Results show that a first good estimate of the length and the size of the blockage can be obtained by a single short duration transient test executed by maneuvering a ball valve located far away from the blockage position.
A stochastic tool for determining the presence of partial blockages in viscoelastic pipelines: first experimental results
MASSARI, CHRISTIAN;FERRANTE, Marco;BRUNONE, Bruno;MENICONI, SILVIA
2014
Abstract
Partial blockages in water pipe networks may contribute to large energy dissipation throughout the system and reduce the service effectiveness for the customers. In this paper, a recently developed stochastic model using transient head measurements for detecting partial blockages in water pipelines is tested with two experimental case studies. The model is a stochastic Successive Linear Estimator (SLE, Yeh et al. 1996) previously used in groundwater hydrology for detecting the heterogeneity pattern of the subsurface. The model provides statistically the best unbiased estimate of diameter distribution due to partial blockages and quantifies the uncertainty associated with these estimates. Tests were carried out at the Water Engineering Laboratory of the University of Perugia (WEL) on two high density polyethylene pipe systems. In the experiments the partial blockages were simulated by placing a smaller diameter pipe of two different lengths between the main pipe. Results show that a first good estimate of the length and the size of the blockage can be obtained by a single short duration transient test executed by maneuvering a ball valve located far away from the blockage position.I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.