In this paper the possibility of using transients to survey a complex transmission system in the city of Mantova, Italy is explored. Transients are generated by pump trip, and the pressure signal is acquired immediately downstream of the pumping station. The pressure signal is analyzed by the wavelet transform to locate the main singularities and evaluate the pressure wave speed of the main pipe. Then a lagrangian model is carried out to evaluate the causes of experimental pressure variations. The comparison between experimental and numerical traces allows checking the efficaciousness of the procedure and diagnosing the network.
Transmission Main Survey by Transient Tests: The Case of Villanova Plan in Mantova (I)
MENICONI, SILVIA;BRUNONE, Bruno;FERRANTE, Marco;CAPPONI, CATERINA;
2014
Abstract
In this paper the possibility of using transients to survey a complex transmission system in the city of Mantova, Italy is explored. Transients are generated by pump trip, and the pressure signal is acquired immediately downstream of the pumping station. The pressure signal is analyzed by the wavelet transform to locate the main singularities and evaluate the pressure wave speed of the main pipe. Then a lagrangian model is carried out to evaluate the causes of experimental pressure variations. The comparison between experimental and numerical traces allows checking the efficaciousness of the procedure and diagnosing the network.File in questo prodotto:
Non ci sono file associati a questo prodotto.
I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.